Product details

SANTAK Photovoltaic power station UPS PT1K-UL,is a kind of Uninterruptible power systemproducts.Its topology was High frequency UPS,Online (dual conversion),Standard model,Single phase input, single-phase output,Its installation method was Vertical/Tower/Horizontal/rack mounted,It belongs to SANTAK PT3000 UL series PT1-3K.Its rated capacity and maximum load power was 1000VA/1000W,Input method was Single phase two-wire+grounded (L+N+PE).Rated voltage was 200/208/220/230/240 VAC (208Vload shedding10%, 200Vload shedding20%).Input Voltage was 160-300V 100%load, 110-160V Linear derating to50%load,Input frequency was 40Hz-70Hz (45Hz-55Hz, 54Hz-66Hz @load>60%),THDI was < 5% Nonlinear full load,Input power factor was ≥ 0.99,Bypass voltage was 187VAC~264VAC,Output voltage was 200/208/220/230/240 VAC (208V load shedding 10%, 200V load shedding 20%),Output accuracy was ± 1 %,Output Connection was Main output (4 x IEC C13) Partition control output (4 x IEC C13),Output frequency range (mains mode) was 50Hz/60Hz adaptive,Output frequency range (battery mode) was 50Hz/60Hz adaptive,Peak output current ratio was 3:1,Output waveform distortion was <1%(linear load;<5%(Nonlinear load),Output power factor was PF = 1,Output waveform was Pure sine output,Overload capacity (mains 25 ℃, output power factor 0.8):100%150% 500ms,Efficiency:online mode:Up to 91%;ECO mode:Up to 96%,Battery voltage × number of batteries:36VDC/3*12V7AH,EBM mode was PTB9032-UL,EBM max number was 4 PCS Max,Hot swappable battery:Y,Battery charging temperature compensation:Y,Battery backup time (25 ℃) was Half load ≤11min;full load ≥4min;1*EBM,Half load ≤55min;full load ≥23min,Battery charging time was 3 hour recharge to 90%,Display:LCD+LED can digitally display load/power/input/output parameters, text and graphical display of operating modes,Rack mounted installation height:2U,Protection level:IP20,Conversion time (mains<>battery) was 0ms@Online mode to Battery mode; 4ms @Online mode to Bypass mode; 10ms @ECO mode to Online mode.Operating temperature:0℃-50℃;0~40℃ full load ;40~50℃ derating(VA&W derating3%/1℃),Relative humidity:20%~90%(No condensation),Its dimensions was 438*445*85.5 mm (2U)mm (W*D*H),Net weight:22.7kg,Audio noise was <50dB @ Distance of 1 meter,Operating altitude was 0~3000m;If UPS is used at an altitude of over 1000m, it must use a decreasing rated output,Execution standards:Safety:IEC/EN 62040-1;(EMC):IEC/EN 62040-2:C1;Performance:IEC/EN62040-3.Product Certification:TLC,CE,CQC.Communication and monitoring include Standard configuration includes USB, RS232, remote power on/off, smart slot, dry contacts, RJ45 (cloud connection), WiFi (optional),Optional Accessories include NMC card (network monitoring card) can be selected; CMC card (Modbus monitoring card); EMP (Temperature and Humidity Acquisition Module); AS400 card (dry connection point card); SPCC_N (Cloud Connection Network Card); WLANdongle (Cloud Connection Card Wifi Module) (requires the purchase of a smart card slot),EPO(optional):N/A,Parallel redundancy(optional):N/A,Software:Winpower,Warranty:3 years .Application scenarios include High end manufacturing of wind turbines, photovoltaic power stations, industrial and commercial energy storage PCS, EMS control systems, outdoor intelligent terminal cabinets, outdoor survey and surveying, rail transit equipment, semiconductor chips, etc

Product Features

  • Global certification adaptation: UL and CE certified, compatible with multiple national power grid standards, supporting five voltage outputs of 200-240V.
  • Efficient and energy-saving design: The online mode efficiency is 93%, PF=1 high power factor, and the load capacity is increased by 30%.
  • Adaptation to harsh environments: Three proof coating circuit board, working temperature 0-50 ℃, operating at an altitude of 3000 meters without derating.
  • Intelligent load management: Independently control output sockets, prioritize critical loads in battery mode, and extend backup time.
  • Multi scenario grid compatibility: Supports three-phase dual live input, 50/60Hz adaptive, suitable for energy storage and photovoltaic systems.
  • Long term battery protection: ABM three-stage charging technology reduces float charge damage and extends battery cycle life.
  • High integration communication capability: Standard dry contact signal, supports multi protocol monitoring, seamlessly integrates with the dynamic ring system.
  • Compact industrial design: 500mm deep body, suitable for short cabinet deployment, saves space and is easy to install and maintain.

Application Scenarios

  • High end manufacturing of wind turbines, photovoltaic power stations, industrial and commercial energy storage PCS, EMS control systems, outdoor intelligent terminal cabinets, outdoor survey and surveying, rail transit equipment, semiconductor chips, etc

Product Parameters

  • Brand:SANTAK
  • Product-type:Uninterruptible power system
  • Series:SANTAK PT3000 UL series PT1-3K
  • Topology:Online (dual conversion)
  • Backup type:Standard model
  • Installation method:Vertical/Tower/Horizontal/rack mounted
  • System:Single phase input, single-phase output
  • Product Category:High frequency UPS
  • Model:PT1K-UL
  • Load power(max):1000VA/1000W
  • Input method:Single phase two-wire+grounded (L+N+PE)
  • Rated voltage:200/208/220/230/240 VAC (208Vload shedding10%, 200Vload shedding20%)
  • Input Voltage:160-300V 100%load, 110-160V Linear derating to50%load
  • Input frequency:40Hz-70Hz (45Hz-55Hz, 54Hz-66Hz @load>60%)
  • THDI:< 5% Nonlinear full load
  • Input power factor:≥ 0.99
  • Bypass voltage:187VAC~264VAC
  • Output voltage:200/208/220/230/240 VAC (208V load shedding 10%, 200V load shedding 20%)
  • Output accuracy:± 1 %
  • Output Connection:Main output (4 x IEC C13) Partition control output (4 x IEC C13)
  • Output frequency range (mains mode):50Hz/60Hz adaptive
  • Output frequency range (battery mode):50Hz/60Hz adaptive
  • Peak output current ratio:3:1
  • Output waveform distortion:<1%(linear load;<5%(Nonlinear load)
  • Output power factor:PF = 1
  • Output waveform:Pure sine output
  • Overload capacity (mains 25 ℃, output power factor 0.8):100%150% 500ms
  • Efficiency:online mode:Up to 91%;ECO mode:Up to 96%
  • Battery voltage × number of batteries:36VDC/3*12V7AH
  • EBM mode:PTB9032-UL
  • EBM max number:4 PCS Max
  • Hot swappable battery:Y
  • Battery charging temperature compensation:Y
  • Conversion time (mains<>battery):0ms@Online mode to Battery mode; 4ms @Online mode to Bypass mode; 10ms @ECO mode to Online mode
  • Display:LCD+LED can digitally display load/power/input/output parameters, text and graphical display of operating modes
  • Battery backup time (25 ℃):Half load ≤11min;full load ≥4min;1*EBM,Half load ≤55min;full load ≥23min
  • Battery charging time:3 hour recharge to 90%
  • Rack mounted installation height:2U
  • Dimensions(W×D×H)(mm):438*445*85.5 mm (2U)
  • Net weight(kg):14.7 kg
  • EBM Dimensions(W×D×H)(mm):438*445*85.5 mm (2U)
  • EBM Net weight(kg):22.7kg
  • Operating temperature:0℃-50℃;0~40℃ full load ;40~50℃ derating(VA&W derating3%/1℃)
  • Storage temperature:-25℃~55℃
  • Relative humidity:20%~90%(No condensation)
  • Audio noise (at a distance of 1 meter):<50dB @ Distance of 1 meter
  • Protection level:IP20
  • Operating altitude:0~3000m;If UPS is used at an altitude of over 1000m, it must use a decreasing rated output
  • Execution standards:Safety:IEC/EN 62040-1;(EMC):IEC/EN 62040-2:C1;Performance:IEC/EN62040-3
  • Product Certification:TLC,CE,CQC
  • Communication and monitoring:Standard configuration includes USB, RS232, remote power on/off, smart slot, dry contacts, RJ45 (cloud connection), WiFi (optional)
  • Optional Accessories:NMC card (network monitoring card) can be selected; CMC card (Modbus monitoring card); EMP (Temperature and Humidity Acquisition Module); AS400 card (dry connection point card); SPCC_N (Cloud Connection Network Card); WLANdongle (Cloud Connection Card Wifi Module) (requires the purchase of a smart card slot)
  • EPO(optional):N/A
  • Parallel redundancy(optional):N/A
  • Software:Winpower
  • Warranty:3 years
  • Note-1:When the altitude is between 3000 meters and 1000 meters, the load rating needs to be reduced. When the ambient temperature is above 25 ℃, the load rating should be reduced by 1% for every 100 meters increase in altitude above 1000 meters.
  • Note-2:Warning: This product is a C2 class UPS and may require installation restrictions or additional measures to suppress RF interference when used in residential areas.
Telephone
4001177032
email
19710409880@139.com
wechat
wechat
Loading...