SANTAK uninterruptible power supplyUPS PT2.2K 2200VA/2200W Certified as compliant:TLC/CE/CQCenergy conservation
SANTAK uninterruptible power supplyUPS PT2.2K,is a kind of Uninterruptible power systemproducts.Its topology was High frequency UPS,Online (dual conversion),Standard model (with built-in battery),Single phase input, single-phase output,Its installation method was Vertical/Tower/Horizontal/rack mounted,It belongs to SANTAK PT3000 series PT1-20K.Its rated capacity and maximum load power was 2200VA/2200W,Input method was Single phase two-wire+grounded (L+N+PE).Rated voltage was 200/208/220/230/240V(Voltage can be set).Input Voltage was 100VAC-276VAC,Input frequency was 40~70Hz,THDI was < 5% Nonlinear full load,Input power factor was ≥ 0.99,Bypass voltage was 187VAC~264VAC,Output voltage was 200/208/220/230/240V(Voltage can be set),Output accuracy was ± 1 %,Output Connection was Main output (1*IEC C19+4*IEC C13) Partition control output (1*IEC C19+2*IEC C13)/(2*IEC C13),Output frequency range (mains mode) was 50 或 60Hz,Automatic sensing or can be set to a fixed frequency output,Output freq
Buy Now
- Telephone:4001177032
- Email:19710409880@139.com
Product details
SANTAK uninterruptible power supplyUPS PT2.2K,is a kind of Uninterruptible power systemproducts.Its topology was High frequency UPS,Online (dual conversion),Standard model (with built-in battery),Single phase input, single-phase output,Its installation method was Vertical/Tower/Horizontal/rack mounted,It belongs to SANTAK PT3000 series PT1-20K.Its rated capacity and maximum load power was 2200VA/2200W,Input method was Single phase two-wire+grounded (L+N+PE).Rated voltage was 200/208/220/230/240V(Voltage can be set).Input Voltage was 100VAC-276VAC,Input frequency was 40~70Hz,THDI was < 5% Nonlinear full load,Input power factor was ≥ 0.99,Bypass voltage was 187VAC~264VAC,Output voltage was 200/208/220/230/240V(Voltage can be set),Output accuracy was ± 1 %,Output Connection was Main output (1*IEC C19+4*IEC C13) Partition control output (1*IEC C19+2*IEC C13)/(2*IEC C13),Output frequency range (mains mode) was 50 或 60Hz,Automatic sensing or can be set to a fixed frequency output,Output frequency range (battery mode) was 50 或 60Hz,Automatic sensing or can be set to a fixed frequency output,Peak output current ratio was 3:1,Output waveform distortion was <1%(linear load;<5%(Nonlinear load),Output power factor was PF = 1,Output waveform was Pure sine output,Overload capacity (mains 25 ℃, output power factor 0.8):102%-125%Load, switch to bypass operation after 10 minutes;125%-150%Load, switch to bypass after 2 seconds; More than 150% load, switch to bypass after 0.3 seconds,Efficiency:online mode:Up to 93%;ECO mode:Up to 98%,Battery voltage × number of batteries:72VDC/6*12V7AH,EBM mode was PTB9062,EBM max number was 4 PCS Max,Hot swappable battery:Y,Battery charging temperature compensation:Y,Battery backup time (25 ℃) was Half load ≤12min;full load ≥4min,Battery charging time was 3 hour recharge to 90%,Display:LCD+LED can digitally display load/power/input/output parameters, text and graphical display of operating modes,Rack mounted installation height:2U,Protection level:IP20,Conversion time (mains<>battery) was 0ms@Online mode to Battery mode; 4ms @Online mode to Bypass mode; 10ms @ECO mode to Online mode.Operating temperature:0℃-50℃;0~40℃ full load ;40~50℃ derating(VA&W derating3%/1℃),Relative humidity:20%~90%(No condensation),Its dimensions was 438*600*85.5 mm (2U)mm (W*D*H),Net weight:40.6,Audio noise was <47dB @ Distance of 1 meter,Operating altitude was 0~3000m;If UPS is used at an altitude of over 1000m, it must use a decreasing rated output,Execution standards:Safety:IEC/EN 62040-1;(EMC):IEC/EN 62040-2:C3;Performance:IEC/EN62040-3.Product Certification:TLC/CE/CQCenergy conservation.Communication and monitoring include Standard configuration includes USB, RS232, remote power on/off, smart slot, dry contacts, RJ45 (cloud connection), WiFi (optional),Optional Accessories include NMC card (network monitoring card) can be selected; CMC card (Modbus monitoring card); EMP (Temperature and Humidity Acquisition Module); AS400 card (dry connection point card); SPCC_N (Cloud Connection Network Card); WLANdongle (Cloud Connection Card Wifi Module) (requires the purchase of a smart card slot),EPO(optional):N/A,Parallel redundancy(optional):N/A,Software:Winpower,Warranty:3 years .Application scenarios include Small and medium-sized enterprises; Large enterprise branch offices; Small scale data centers such as bank branches; Switch; NAS storage; Network server; VoIP; Communication equipment; Automated equipment; Office PC terminal; Medical biochemistry laboratory instruments and equipment, etc
Product Features
- Efficient dual conversion architecture: Online mode efficiency of 95% -96%, output PF=1, load capacity increased by 30%, significant energy saving and consumption reduction.
- Full scenario power purification: solves 11 types of power problems such as power outages and harmonics, outputs pure sine waves, and ensures zero interruption of equipment.
- Flexible input/output configuration: supports four modes including three in single out and three in three out, adapting to global power grids and multi scenario needs.
- Intelligent battery management: 16-40 batteries can be adjusted, and the charging current can be flexibly set between 1-13A to extend battery life and endurance.
- Adaptation to harsh environments: Three proof coated circuit board, stable operation at 50 ℃ high temperature, passed seismic and industrial reliability tests.
- Intelligent load grading: prioritize ensuring power supply for critical equipment, and extend the backup time for core loads in battery mode.
- Human computer interaction optimization: touch LCD screen+multi protocol interface (USB/RS232/dry contacts), supporting remote monitoring and virtualization platform integration.
- Compact and highly compatible design: Rack mounted with a height of only 2U and a depth of<600mm, compatible with standard cabinets, saving deployment space.
Application Scenarios
- Small and medium-sized enterprises; Large enterprise branch offices; Small scale data centers such as bank branches; Switch; NAS storage; Network server; VoIP; Communication equipment; Automated equipment; Office PC terminal; Medical biochemistry laboratory instruments and equipment, etc
Product Parameters
- Brand:SANTAK
- Product-type:Uninterruptible power system
- Series:SANTAK PT3000 series PT1-20K
- Topology:Online (dual conversion)
- Backup type:Standard model (with built-in battery)
- Installation method:Vertical/Tower/Horizontal/rack mounted
- System:Single phase input, single-phase output
- Product Category:High frequency UPS
- Model:PT2.2K
- Load power(max):2200VA/2200W
- Input method:Single phase two-wire+grounded (L+N+PE)
- Rated voltage:200/208/220/230/240V(Voltage can be set)
- Input Voltage:100VAC-276VAC
- Input frequency:40~70Hz
- THDI:< 5% Nonlinear full load
- Input power factor:≥ 0.99
- Bypass voltage:187VAC~264VAC
- Output voltage:200/208/220/230/240V(Voltage can be set)
- Output accuracy:± 1 %
- Output Connection:Main output (1*IEC C19+4*IEC C13) Partition control output (1*IEC C19+2*IEC C13)/(2*IEC C13)
- Output frequency range (mains mode):50 或 60Hz,Automatic sensing or can be set to a fixed frequency output
- Output frequency range (battery mode):50 或 60Hz,Automatic sensing or can be set to a fixed frequency output
- Peak output current ratio:3:1
- Output waveform distortion:<1%(linear load;<5%(Nonlinear load)
- Output power factor:PF = 1
- Output waveform:Pure sine output
- Overload capacity (mains 25 ℃, output power factor 0.8):102%-125%Load, switch to bypass operation after 10 minutes;125%-150%Load, switch to bypass after 2 seconds; More than 150% load, switch to bypass after 0.3 seconds
- Efficiency:online mode:Up to 93%;ECO mode:Up to 98%
- Battery voltage × number of batteries:72VDC/6*12V7AH
- EBM mode:PTB9062
- EBM max number:4 PCS Max
- Hot swappable battery:Y
- Battery charging temperature compensation:Y
- Conversion time (mains<>battery):0ms@Online mode to Battery mode; 4ms @Online mode to Bypass mode; 10ms @ECO mode to Online mode
- Display:LCD+LED can digitally display load/power/input/output parameters, text and graphical display of operating modes
- Battery backup time (25 ℃):Half load ≤12min;full load ≥4min
- Battery charging time:3 hour recharge to 90%
- Rack mounted installation height:2U
- Dimensions(W×D×H)(mm):438*600*85.5 mm (2U)
- Net weight(kg):25
- EBM Dimensions(W×D×H)(mm):438*600*85.5 mm (2U)
- EBM Net weight(kg):40.6
- Operating temperature:0℃-50℃;0~40℃ full load ;40~50℃ derating(VA&W derating3%/1℃)
- Storage temperature:-25℃~55℃
- Relative humidity:20%~90%(No condensation)
- Audio noise (at a distance of 1 meter):<47dB @ Distance of 1 meter
- Protection level:IP20
- Operating altitude:0~3000m;If UPS is used at an altitude of over 1000m, it must use a decreasing rated output
- Execution standards:Safety:IEC/EN 62040-1;(EMC):IEC/EN 62040-2:C3;Performance:IEC/EN62040-3
- Product Certification:TLC/CE/CQCenergy conservation
- Communication and monitoring:Standard configuration includes USB, RS232, remote power on/off, smart slot, dry contacts, RJ45 (cloud connection), WiFi (optional)
- Optional Accessories:NMC card (network monitoring card) can be selected; CMC card (Modbus monitoring card); EMP (Temperature and Humidity Acquisition Module); AS400 card (dry connection point card); SPCC_N (Cloud Connection Network Card); WLANdongle (Cloud Connection Card Wifi Module) (requires the purchase of a smart card slot)
- EPO(optional):N/A
- Parallel redundancy(optional):N/A
- Software:Winpower
- Warranty:3 years
- Note-1:When the altitude is between 3000 meters and 1000 meters, the load rating needs to be reduced. When the ambient temperature is above 25 ℃, the load rating should be reduced by 1% for every 100 meters increase in altitude above 1000 meters.
- Note-2:Warning: This product is a C2 class UPS and may require installation restrictions or additional measures to suppress RF interference when used in residential areas.