SANTAK room cooling systems SCC012UPE1 12.5kW(return air24℃,RH50%) Air cooled direct expansion Constant temperature and humidity3780m³/h @100Pa;
SANTAK room cooling systems,SCC012UPE1,12.5kW(return air24℃,RH50%),Air cooled direct expansion,Constant temperature and humidity,Air supply volume3780m³/h @100Pa;EC centrifugal fan,Certified as compliantCCC、CQC、CRAA
Buy Now
- Telephone:4001177032
- Email:19710409880@139.com
Product details
SANTAK room cooling systems SCC012UPE1,is a kind of Precision air conditioner and humidification systemsproducts.,It belongs to SANTAK Castle (SCC)Series Fixed frequency small precision air conditioner7.5-20kW.Power input was 380/3p/50hz,Product Category was Air cooled direct expansion,Cooling method was Constant temperature and humidity,Air supply mode:Step forward and provide air supply,Total cooling capacity:12.5kW(return air24℃,RH50%),Apparent cooling capacity was 11.25kW(return air24℃,RH50%),Sensible heat ratio was 0.9,Air supply volume:3780m³/h @100Pa;,Refrigeration tube was 30/60m(Standard parts/with extension components),Indoor and outdoor unit height difference was 20/-5m,Refrigerant was R410A,Standard pipe diameter:22/16(Tracheal/liquid tube)(mm),Indoor unit Dimensions:650*450*1800mm(W*D*H),Expansion valve type:Electronic expansion valve,Compressor brand:Copeland,Compressor number:1,Compressor type was Fixed frequency rotary compressor,Compressor power was -,Fan brand was ZIEHL-ABEGG,Fan number:1,Fan type:EC centrifugal fan,Wind turbine input power was 0.86kW,Air filter screen was G4,Electric heating type was PTC,Heating capacity was 3kW,Number of heater stages was 1,Humidification amount was 3kg/hr,Humidification type was electrode,Humidification inlet pipe threaded interface wasG1/2"internal thread,Display screen size was 4.3-inch LCD display screen,Number of parallel machines was 32,Communication port was RS485,Noise was 66dB(A) @1m,Evaporator form:A/V,Heat exchanger treatment was hydrophilic aluminum foil,Net weight:132/138kg,Outdoor unit model was CS016F,Power input was 220V/1P/50HZ,Power input method was Follow indoor unit,Number of outdoor units per unit:1,Heat exchanger treatment was acrylic resin,Maximum ambient temperature was 47℃,Minimum supported ambient temperature:-15℃/-35℃ (standard/low temperature components),Fan type:AC axial flow fan,Fan drive mode:Standard speed regulator,Noise:60dB(A),Net weight:53kg,Distribution parameter:16.5AConstant temperature and humidity type,Recommended Circuit Breaker:,Recommended cables:4*4.0mm²+1*4.0mm²,Function include Standard configuration for standby, cooling, humidification, heating, dehumidification, cooling humidification, dehumidification heating, and heating humidification units: water leakage detection, sight glass, dry filter, phase sequence protection function, fan airflow loss alarm, filter screen dirt blockage alarm, automatic power on/off, group control, liquid circuit solenoid valve (the unit does not come with fan sinking components and needs to be purchased separately),Optional Accessories include Low temperature component/extension component/5m copper pipe installation package,Pipe routing method was Lower takeover+later takeover,Drainage pipe diameter was Condensate drain pipe:outside diameter25mm,inside diameter19mm,Certification:CCC、CQC、CRAA,Warranty was 1 Years,Application scenarios include Computer room, equipment room, wiring room, UPS room, enterprise computer room, data room, medium and large data center, rail transit station computer room, laboratory, testing room, constant temperature and humidity storage room
Product Features
- Efficient and energy-saving design: EC centrifugal fan+speed regulating axial flow fan, CQC first level energy efficiency, sensible heat ratio of 0.9+.
- Accurate environmental control: electronic expansion valve+high air volume with small enthalpy difference, temperature control ± 1 ℃, humidity ± 5%.
- Wide temperature operation capability: standard-15℃~45℃operation, optional low-temperature components support -35 ℃ severe cold environment.
- Intelligent operation and maintenance management: 4.3-inch LCD screen+RS-485 group control, supporting remote monitoring and historical event tracing.
- Quick installation and deployment: Pre charged R410A refrigerant+quick interface, welding free installation, efficiency increased by 40%.
- Flexible structure adaptation: front and rear/bottom pipes are optional, and the wind cap is integrated to adapt to compact space layout.
- Industrial grade reliability: high-efficiency compressor+dust-proof filter, 24 × 365 uninterrupted operation, three-year warranty.
- Environmental and low-carbon certification: R410A refrigerant+CCC/CRAA certification, green and energy-saving, in compliance with environmental standards.
Application Scenarios
- Computer room, equipment room, wiring room, UPS room, enterprise computer room, data room, medium and large data center, rail transit station computer room, laboratory, testing room, constant temperature and humidity storage room
Product Parameters
- Brand:SANTAK
- Product-type:Precision air conditioner and humidification systems
- Series:SANTAK Castle (SCC)Series Fixed frequency small precision air conditioner7.5-20kW
- Model:SCC012UPE1
- Power input:380/3p/50hz
- Product Category:Air cooled direct expansion
- Cooling method:Constant temperature and humidity
- Air supply mode:Step forward and provide air supply
- Total cooling capacity:12.5kW(return air24℃,RH50%)
- Apparent cooling capacity:11.25kW(return air24℃,RH50%)
- Sensible heat ratio:0.9
- Air supply volume(m³/h @100Pa):3780m³/h @100Pa;
- Refrigeration tube:30/60m(Standard parts/with extension components)
- Indoor and outdoor unit height difference:20/-5m
- Refrigerant:R410A
- Standard pipe diameter:22/16(Tracheal/liquid tube)(mm)
- Indoor unit Dimensions(W×D×H)(mm):650*450*1800
- Expansion valve type:Electronic expansion valve
- Compressor brand:Copeland
- Compressor number:1
- Compressor type:Fixed frequency rotary compressor
- Compressor power:-
- Fan brand:ZIEHL-ABEGG
- Fan number:1
- Fan type:EC centrifugal fan
- Wind turbine input power:0.86kW
- Air filter screen:G4
- Electric heating type:PTC
- Heating capacity:3kW
- Number of heater stages:1
- Humidification amount:3kg/hr
- Humidification type:electrode
- Humidification inlet pipe threaded interface:G1/2"internal thread
- Display screen size:4.3-inch LCD display screen
- Number of parallel machines:32
- Communication port:RS485
- Noise dB (A) (1-meter free field):66dB(A) @1m
- Evaporator form:A/V
- Heat exchanger treatment:hydrophilic aluminum foil
- Net weight:132/138kg
- Outdoor unit model:CS016F
- Power input:220V/1P/50HZ
- Power input method:Follow indoor unit
- Number of outdoor units per unit:1
- Heat exchanger treatment:acrylic resin
- Outdoor unit Dimensions(W×D×H)(mm):728*405*1370
- Maximum ambient temperature:47℃
- Minimum supported ambient temperature:-15℃/-35℃ (standard/low temperature components)
- Fan type:AC axial flow fan
- Fan drive mode:Standard speed regulator
- Noise:60dB(A)
- Net weight:53kg
- Distribution parameter FLA:16.5AConstant temperature and humidity type
- Recommended Circuit Breaker:
- Recommended cables:4*4.0mm²+1*4.0mm²
- Function:Standard configuration for standby, cooling, humidification, heating, dehumidification, cooling humidification, dehumidification heating, and heating humidification units: water leakage detection, sight glass, dry filter, phase sequence protection function, fan airflow loss alarm, filter screen dirt blockage alarm, automatic power on/off, group control, liquid circuit solenoid valve (the unit does not come with fan sinking components and needs to be purchased separately)
- Optional Accessories:Low temperature component/extension component/5m copper pipe installation package
- Pipe routing method:Lower takeover+later takeover
- Drainage pipe diameter:Condensate drain pipe:outside diameter25mm,inside diameter19mm
- Certification:CCC、CQC、CRAA
- Warranty:1 Years
- Note-1:When no hood is added, the indoor units for upper and lower air supply have the same size; The hood component of the upper air supply fan model is an optional accessory, with a standard height of 412mm
- Note-2:If the outdoor ambient temperature is below minus 15 degrees, a low-temperature kit needs to be selected. If the equivalent pipe length between indoor and outdoor units is greater than 30m, a matching extension component needs to be selected